In a perfect world everyone would have a PERFECT EARTH...
Now with WRICON they can!


EARTHING SYSTEMS - FOR ALL INSTALLATIONS

THE WRICON EARTHING SYSTEM provides the means to locate the entire system completely within the structure, thus providing a location away from any possibility of accidental damage or unauthorised disconnection.

Safe and effective electrical earthing is the essential requirement of all electrical installations, and the use of reinforced concrete foundations is an excellent method of achieving this aim.

The WRICON Earthing System permits the installation of an indestructible, totally reliable and constant electrical earth. The heart of the WRICON Earthing System is the unique Earthing Terminal Plate which allows earthing to the building frame (foundations or rebar) to be installed easily, simply and very professionally by any person who can weld proficiently. Earthing to the building frame (foundations or rebar) is permitted under the E.W.R. of New Zealand and the use of WRICON Earthing System has obvious advantages:-

  1. Reinforcing steel in concrete foundations provides an indestructible earth electrode.
  2. WRICON earth lead is safely cast within the concrete and cannot be severed by other trades digging for services and is also secure from theft.
  3. CADWELD welded connections (unlike compression connections) do not deteriorate. Additionally the tinned solid copper head lug, bronze terminal plate and insulated earth lead incorporated in the WRICON Earthing System prevent galvanic corrosion and high resistance joints, permanently.
  4. Lower resistance to earth than will be obtained by conventional methods and is much less subject to seasonal changes.

TYPE/CAT NO
WRICON Cable
Mains Cable
1 Sec Current Rating
3 Sec Current Rating
Lug Diameter
Terminal Thread Size
Terminal Depth
C / 16
16mm2
4mm2 - 50mm2
2.3 KA
1.3 KA
10mm
M8
16mm
C / 35
35mm2
70mm2 - 120mm2
5.0 KA
2.9 KA
10mm
M8
16mm
C / 50
50mm2
120mm2 - 150mm2
7.1 KA
4.1 KA
16mm
M10
20mm
C / 70
70mm2
150mm2 - 180mm2
10 KA
5.8 KA
16mm
M10
20mm
C / 95
95mm2
185mm2 - 240mm2
13.6 KA
7.8 KA
16mm
M10
20mm
C / 120
120mm2
240mm2 - 630mm2
17.2 KA
9.9 KA
16mm
M12
20mm
Special Note

  • Installer to notify local supply authority for inspection of welded termination to rebar before concrete is poured.
  • Suffix BT refers to a Bare Tail Wricon minus head plate.

WRICON by Contract Connections